www.eaton.com/DXUPS USER MANUAL ONLINE UPS 6000L(XL)/10000L(XL) Uninterruptible Power Supply
8 Important Note: If the UPS is used in Single Mode, JP1 and JP2 must be connected by 10AWG (6mm2). If the UPS is used in Parallel Mode,
9 Important Note: If the UPS is used in Single Mode, JP1 and JP2 must be connected by 10AWG (6mm2). If the UPS is used in Parallel Mode, the Jumper be
10 1) DC breaker must be connected between the battery pack and the UPS. The capacity of breaker must be not less than the data specified in the gener
11 2.4 Parallel operation 1. Brief introduction of the redundancy N+X is currently the most reliable power supply structure. N represents the minimum
12 3. Parallel operation To perform the general operation, follow the stand-alone operating requirement: 1) Startup: The units transfer to INV mode si
13 2) To power on the UPS by simply pressing the “ON” button continuously for more than 1 second. 3) When being powered on, the UPS will perform sel
14 to power off the UPS. 2) When being powered off, the UPS will perform self-diagnosis, the Load/Battery level LEDs will be turned on and then off o
15 before supplying power of the generator to the UPS (be sure that the UPS is in idle mode). Then turn on the UPS according to the start-up procedure
16 The display panel in bypass mode is shown in the following diagram. The utility power LED and the bypass LED are lit. The displayed number of the l
17 6. Communication Port Intelligent slot This series is equipped with an intelligent slot for Webpower (optional accessory) or ot
CONTENTS1.Brief introduction2. Installation171.1 System and model description11.2 Description of commonly used symbols21.3 Appearance31.4 Product s
18 Pin number Function description I/O 3 Rx input 2 Tx output 5 Ground GND DB-9 pin assignment: Optional AS400 interface This optional AS400 ca
19 Data-Line Surge Protection The built-in data-line surge suppression on the rear panel completes your system protection. It provides an easy way to
20 ● Replace batteries with the same number and same type of batteries. ● Do not replace the battery individually. All the batteries should be re
21 Therefore, before any maintenance and repairs work is carried out, switch off the breaker of the battery pack or disconnect the jumper wire of conn
22 The utility power LED flashes The voltage or frequency of the utility power is out of the input range of the UPS. The UPS is running in battery mod
23 When you contact the service center, please provide the following information: ● Model No. and the serial No. of the UPS; ● The date when th
24 Appendix 1: display panel n Power ON/OFF: To turn on the UPS simply by pressing the “ON” button on the front panel continuously for 1 second. Pres
25 Appendix 2: The corresponding form of the LED display LED display No. Operating state 1# 2# 3# 4# 5# 6# 7# 8# 9# 10# Alarm warning 1 0~35% Load ca
26 ●: Solid ON ★: Flash ↑: LED display and alarm warning are dependent on other conditions. 14 Utility power abnormal ↑ ↑ ↑ ↑ ● ★
27 614-03753-01
1 1. Brief introduction 1.1 System and model description This Online Series is an uninterruptible power supply incorporating double-conversion technol
2 1.3 Appearance Nation and Explanation Nation Explanation Nation Explanation Alert you to pay special attention Protective ground C
4 ● Electrical performance Input Model Voltage Frequency Power Factor 6000L(XL)/ 10000L(XL) Single-phase (46~54)/(56~64)Hz >0.98 (Full load)
5 2. Installation 2.1 Unpacking and inspection 1) Unpack the packaging and check the package contents. The shipping package contains: ● A UPS ● A U
6 installation. The battery breaker also needs to be cut off if it is a long backup time model (“XL” model). ● Open the terminal block cover located
7 ● To connect the load with the UPS, please turn off all the loads first, then perform the connection and finally turn on the loads one by one. ● N