Eaton PW102SW0U150 Specifications

Browse online or download Specifications for Power distribution units (PDUs) Eaton PW102SW0U150. Eaton PW102SW0U150 power distribution unit PDU User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - June 20, 2007

IPV42 & IPV70 Series Manual Version 2.0.B June 20, 2007

Page 2

Page 10 of 68 4. Load Current Display – alternates every four seconds to display the current for each outlet section (single-phase units) or phase (t

Page 3

Page 11 of 68 1.9 Accessories Part Number Description SENSOR-T1-10 Temperature sensor wired to Temperature 1 input. SENSOR-T1H1-10 Same as SENSOR-T1

Page 4 - 1 Description

Page 12 of 68 2 Getting Started 2.1 Hardware Setup 1. To use the RS232 serial interface, connect the serial cable provided to the port labeled Serial

Page 5 - 1.3 Features

Page 13 of 68 Serial channels will use a baud rate of 9600 This board's MAC Address is 00:04:F3:00:21:69 After board is reset, start-up cod

Page 6 - Page 6 of 68

Page 14 of 68 2- *Unit IP Address: 192.9.200.201 3- *Subnet Mask: 255.255.255.0 4- *Default Gateway: 192.9.200.254 -- MAC Address:

Page 7 - 1.6.2 IPV70 Series

Page 15 of 68 3. A home screen will be displayed with a navigation bar on the left and the unit status on the right. Clicking any of the links in t

Page 8 - 1.7 Mounting

Page 16 of 68 2.3.2 Telnet Interface The telnet interface is text-driven and uses a menu structure almost identical to that accessed via serial connec

Page 9 - 1.8 Physical Features

Page 17 of 68 3 Serial/Telnet Text Interfaces The serial and telnet interfaces use the same text navigation menu to view outlet status and logs, issu

Page 10

Page 18 of 68 After logging in, the Main Menu should be displayed: Enter UserName: Admin Enter Password: *** Pulizzi IPC3600 Version 2.0.B ---------

Page 11 - 1.9 Accessories

Page 19 of 68 -- Outlet 1 Command Choices -- 1- Immediate On 2- Immediate Off 3- Reboot -- Other Choices -- <ESC> = Back <s> = Out

Page 12 - 2 Getting Started

Page 2 of 68 1 Description...4 1.1 Intr

Page 13

Page 20 of 68 Select Item Number: 3.2.1 Outlet Configuration -- Outlet Configuration Sub Menu -- Name

Page 14 - 2.3.1 Web Interface

Page 21 of 68 point before a particular outlet turns on. A Sequence Off command works backwards and first turns off the outlet with the largest Seque

Page 15

Page 22 of 68 3.2.3 Auto Scheduler -- Auto Scheduler Sub Menu -- Outlet/Group Command Every Day Time ---

Page 16 - 2.3.3 SNMP Interface

Page 23 of 68 Select 1 - 7 or press <Enter> to skip: 1 Press <Esc> anytime to cancel all. Time format: HH:MM on a 24-hour clock. Example

Page 17

Page 24 of 68 6- Display VA Measurements -- Other Choices -- <ESC> = Back <s> = Outlet/Environmental status Select Item Number: 3.2.5

Page 18 - 3.1 Outlet Control Menu

Page 25 of 68 Control Outlet/Group: If the sensor only needs to be used to report the temperature readings, this setting should be No. If it is set t

Page 19

Page 26 of 68 later changed, control from sensors or switches will not work until they are reconfigured with the new name. State: This may be set to e

Page 20 - 3.2.1 Outlet Configuration

Page 27 of 68 1 VA Monitor Interval Outlet Section Voltage Threshold Current Threshold Ctrl Outlet/Group

Page 21 - 3.2.2 Outlet Groups

Page 28 of 68 Switch 3: Closed Any key to update display <ESC> = Back This menu option displays the up-to-date temperature, humidity, and cont

Page 22 - 3.2.3 Auto Scheduler

Page 29 of 68 4- Time: 07:56 5- Date: 03/01/2007 6- Timeout in Seconds: 300 7- Fahrenheit/Celsius: Fahrenheit 8- D

Page 23 - 3.2.5 Environmental Settings

Page 3 of 68 3.3.4 Log Manager...33 3.3.4.1 View Log/Alert

Page 24

Page 30 of 68 Note that many of these network settings require a soft reboot to take effect (choose Soft Reboot from the Main Menu). Use DHCP: This o

Page 25

Page 31 of 68 Ping Interval: May be any integer from 5 to 60 minutes; changes take effect immediately. Serial Baud Rate: May be 9600, 19200, or 3840

Page 26 - 3.2.5.4 Power Monitor Setup

Page 32 of 68 the serial, telnet, or web interfaces three times in a row due to an invalid username or an invalid password. Trap Outlet Activity: This

Page 27

Page 33 of 68 enabled, and the numbers of the outlets to which the user will have access. Here is an example: Select Item Number: 3 Enter New Outle

Page 28 - 3.3 Unit Configuration

Page 34 of 68 Select Item Number: The Log Manager contains all settings related to logs and alerts. Logs are kept of the items selected under the L

Page 29 - 3.3.2 Network Settings

Page 35 of 68 -- Other Choices -- <ESC> = Back <s> = Outlet/Environmental status Select Item Number: Events To Log - User Login/Logou

Page 30

Page 36 of 68 3.3.5 Administrative Utilities -- Administrative Utilities -- 1- Update Firmware 2- Show Firmware version 3- Set System Defaults -- Ot

Page 31 - 3.3.2.1 SNMP Menus

Page 37 of 68 Press any key in 5 seconds to change these settings. Pulizzi FTP Server ready. At this point the FTP server is ready to receive the f

Page 32 - 3.3.3 User Manager

Page 38 of 68 7 Outlet 7 On 8 Outlet 8 On -- Other Choices -- <ESC> = Back <s> = Outlet

Page 33 - 3.3.4 Log Manager

Page 39 of 68 4 Web Interface The web interface uses graphical navigation to view outlet status and logs, issue outlet commands, and change settings.

Page 34

Page 4 of 68 1 Description 1.1 Introduction The Pulizzi Engineering Inc. IPV series of Intelligent Power Controller™ products provide distribution of

Page 35

Page 40 of 68 Outlet Section Navigation Buttons: The status for one outlet section at a time is displayed on the screen. When connected to a 16- or 2

Page 36 - 3.3.5.1 Update Firmware

Page 41 of 68 4.3 Outlet Control Outlet commands and global commands can be issued from the Outlet Control screen. Outlet Commands: To issue an outle

Page 37 - 3.4.1 Outlet Section

Page 42 of 68 4.4 Group Control Groups of outlets can be set up in the Group Configuration screen and can be controlled from this Group Control scree

Page 38 - 3.5 Choose Strapping Device

Page 43 of 68 4.5 Outlet Configuration Note: To select outlets from an outlet section different than what is shown, first press Save Changes to store

Page 39 - 4 Web Interface

Page 44 of 68 Sequence: Integers from 0 to 999 are valid (units are seconds). Outlets may be sequenced on or off using Global Sequence On and Global

Page 40 - 4.2 Power Log

Page 45 of 68 4.6 Group Configuration Name: May be up to 20 characters. Clear this field and press Save Changes to remove the group. Outlet Access:

Page 41 - 4.3 Outlet Control

Page 46 of 68 4.7 Scheduler Configuration The Scheduler screen allows daily or weekly events to be set up for outlets or groups of outlets. Outlet/Gr

Page 42 - 4.4 Group Control

Page 47 of 68 4.8 Environmental Configuration 4.8.1 Temperature and Humidity Settings Temperature and humidity probes are accessories that can be pur

Page 43 - 4.5 Outlet Configuration

Page 48 of 68 Enabled: A sensor must be enabled before the readings can be displayed. High Threshold: Whenever the readings cross above this threshold

Page 44

Page 49 of 68 Outlet/Group to ON: This may be set to either Yes or No. If the setting is Yes, the outlet or group will be turned on whenever the cont

Page 45 - 4.6 Group Configuration

Page 5 of 68 telnet connection may also be launched in Windows by typing “telnet” in a Command Prompt window. Terminal Emulation Program: Serial commu

Page 46 - 4.7 Scheduler Configuration

Page 50 of 68 4.9 Unit Configuration Unit Name: Up to 20 characters may be used to name the unit. Strapping ID: Each unit connected together on a str

Page 47

Page 51 of 68 Unit Day of Week: Select the day of the week that matches the Date. This is important when scheduling events and sending logs. Power Lo

Page 48

Page 52 of 68 4.10 Network Configuration Note that many of the following Network Settings require a soft reboot to take effect (select Soft Reboot fr

Page 49

Page 53 of 68 MAC Address: This value is unique to each IPV unit and cannot be changed from this screen. If customization is necessary, see the instr

Page 50 - 4.9 Unit Configuration

Page 54 of 68 Ping Enabled: This option may be either Enabled or Disabled; changes take effect immediately. If Ping is Enabled, the unit individuall

Page 51

Page 55 of 68 Trap User Login: This option may be either Enabled or Disabled. When Enabled, a trap will be sent to the Trap IP Address each time a us

Page 52 - 4.10 Network Configuration

Page 56 of 68 4.11 User Configuration Up to 11 non-Admin users may be set up with separate user accounts and access rights. These users will be able

Page 53

Page 57 of 68 4.12 Log Configuration Log Configuration contains all settings related to logs and alerts. Logs are kept of the items selected under E

Page 54

Page 58 of 68 Send Alerts To 2: Up to 30 characters may be used to specify a second email address for all alerts to be sent to. Send Log From: Up to 3

Page 55

Page 59 of 68 Alerts To Send - Power Monitor Threshold: This option may be either Enabled or Disabled. When Enabled, an email alert will be sent each

Page 56 - 4.11 User Configuration

Page 6 of 68 1.4 Electrical Specifications The following table details the IPV electrical specifications. The two-letter version code corresponds to

Page 57 - 4.12 Log Configuration

Page 60 of 68 Strapping is an advanced feature of the IPV42 & IPV70 products. See the Strapping section for more information.

Page 58

Page 61 of 68 5 SNMP Interface The IPV42/IPV70 SNMP interface conforms to version 2c of the SNMP protocol. To use this interface, the IPV must first

Page 59 - 4.13 Select Strapping Device

Page 62 of 68 6 Strapping Strapping is an advanced feature of the IPV42 & IPV70 products. Units with “-EP” in the part number have four RJ45-styl

Page 60 - Page 60 of 68

Page 63 of 68 6. Once the connection has been initialized, all of the menu options display the secondary unit’s data. To return to the primary unit,

Page 61 - 5 SNMP Interface

Page 64 of 68 7 Advanced Boot Configuration IPV42 & 70 units offer advanced configuration options via the serial interface. Follow these steps t

Page 62 - 6 Strapping

Page 65 of 68 Static IP address [192.9.200.201]? Subnet Mask IP address [255.255.255.0]? Gateway address IP address [192.9.200.254]? SECURITY PARA

Page 63 - Page 63 of 68

Page 66 of 68 Select the Number of Outlets: Select the number of outlets that are present on your IPV42 or IPV70 unit. Strapping ID: This setting is t

Page 64

Page 67 of 68 Appendix A – Contact Sensor Wiring Units with “-EP” in the part number have four RJ45-style jacks on the face, one of which is labeled “

Page 65

Page 68 of 68 Appendix B – Recovering From a Lost Password Passwords can only be recovered from the serial interface. Use the following steps to chan

Page 66

Page 7 of 68 1.5 Environmental Specifications Operating Temperature Range: 0 to 50°C Storage Temperature Range: -40 to 65°C Operating Humidity Range:

Page 67

Page 8 of 68 1.7 Mounting IPV42 and IPV70 come with SUB-HRDWARE-017 mounting brackets attached. These mounting brackets allow the units to be mounted

Page 68

Page 9 of 68 1.8 Physical Features 1. Detachable Mounting Brackets 2. 8, 16, or 24 Receptacles – IEC C13 or NEMA 5-15R 3. LED Indicators – sh