Installation and user
manual
JBUS/MODBUS
communication
card
www.mgeups.com
T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
MGE UPS SYSTEMS
66061
JBUS/MODBUS
Page view 0
1 2 3 4 5 6 ... 67 68

Summary of Contents

Page 1 - JBUS/MODBUS

51029066EN/BB - Page 1Installation and usermanualJBUS/MODBUScommunicationcardwww.mgeups.comT H E U N I N T E R R U P T I B L E P O W E R P R O

Page 2 - Page 2 - 51029066EN/BB

Page 10 - 51029066EN/BB2. Installation2.1 Configuration of the JBUS/MODBUS communication parametersIf needed, it is possible to modify the default val

Page 3 - Introduction

51029066EN/BB - Page 112. Installation3 - Set the terminal with the following communication parameters: 9600 baud rate, even parity, 1 stop bit and 7

Page 4 - Foreword

Page 12 - 51029066EN/BB2. Installation2.2 Return to the default JBUS/MODBUS parametersTo return to the default parameters (see §1.4) of the JBUS/MODBU

Page 5 - Contents

51029066EN/BB - Page 132.3 RS232 link configuration and connection2. InstallationDefault connection:Transmist dataReceive dataIf necessary, it is pos

Page 6 - 1. Presentation

Page 14 - 51029066EN/BB2. Installation2.4 RS485 link configuration and connectionFor proper operation, the polarity of EIA RS485 2-wire and 4-wire lin

Page 7

51029066EN/BB - Page 152. InstallationSA2 switches are used to make the termination and the polarity of the RS485 link:(all to OFF position)2 wiresco

Page 8

Page 16 - 51029066EN/BB2. InstallationDiagram of a 2-wire inter-cubicle connection5VRpRaRp0V5VRpRaRp0V5VRpRaRp0VL- L-L+ L+L- L-L+ L+2376894523768945po

Page 9

51029066EN/BB - Page 172. InstallationCard settings of an intermediate cubicle in 2 wiresLink without polarity and without termination.Card settings

Page 10 - 2. Installation

Page 18 - 51029066EN/BB2. InstallationDiagram of a 4-wire inter-cubicle connection5VRpRp0V5VRpRaRp0V5VRpRaRp0VT- R-T+ R+R- R-R+ R+2376842376845VRpRaRp

Page 11

51029066EN/BB - Page 192. InstallationCard settings of an intermédiate cubicle in 4 wiresLink without polarity and without termination.Card settings

Page 12

Page 2 - 51029066EN/BB

Page 13

Page 20 - 51029066EN/BB2. Installation2.5 Card installationIt is not necessary to turn the UPS or theSTS off.1. Using a screwdriver, remove the coverf

Page 14

51029066EN/BB - Page 213. OperationThe JBUS/MODBUS communication card can be inserted in all products equipped with communication slots.For each of t

Page 15

Page 22 - 51029066EN/BB3. OperationMeasurements tableDescription of the physical quantity Word UnitI mains 1 100 AI output 109 AU mains 1 115 VU outpu

Page 16

51029066EN/BB - Page 233.2 In Galaxy 3000Status table3. OperationStatus description Status to 0 Status to 1 Word BitLoad protected no yes 40 0UPS cou

Page 17

Page 24 - 51029066EN/BB3. OperationStatus description Status to 0 Status to 1 Word BitMains 2 frequency out of tolerance no yes 46 9Mains 2 voltage ou

Page 18

51029066EN/BB - Page 25Measurements tableDescription of the physical quantity Word UnitI1 (I phase 1) mains 1 100 AI2 (I phase 2) mains 1 101 AI3 (I

Page 19

Page 26 - 51029066EN/BB3. Operation3.3 In Galaxy PWStatus tableStatus description Status to 0 Status to 1 Word BitLoad protected no yes 40 0UPS couple

Page 20

51029066EN/BB - Page 27Status description Status to 0 Status to 1 Word BitMains 1 input switch (Q1) closed open 44 3Mains 1 voltage out of tolerance

Page 21 - 3. Operation

Page 28 - 51029066EN/BB3. OperationMeasurements tableDescription of the physical quantity Word UnitI1 (I phase 1) mains 1 100 AI2 (I phase 2) mains 1

Page 22

51029066EN/BB - Page 29Description of the physical quantity Word UnitNominal backup time 148 mnBattery backup time 149 mnBattery room temperature 14A

Page 23

51029066EN/BB - Page 3IntroductionThank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.The JBUS/MODBUS card has be

Page 24

Page 30 - 51029066EN/BB3. OperationStatus description Status to 0 Status to 1 Word BitSource 2 out of tolerance no yes 1002 ETransfert valid no yes 10

Page 25

51029066EN/BB - Page 313. OperationMeasurements tableDescription of the physical quantity Word UnitU12 source 1 1100 VU23 source 1 1101 VU31 source 1

Page 26

Page 32 - 51029066EN/BB4. TroubleshootingProblemThe diagnostic LED 6remains always OFF.The diagnostic LED 6remains always ON.JBUS/RS232 communicat

Page 27

51029066EN/BB - Page 33ALine termination ... 14-19BSA2 microswitches settings for RS485 configur

Page 28

Page 34 - 51029066EN/BB

Page 29

51029066FR/BB - Page 1Manuel d'installationet d'utilisationCarte decommunicationJBUS/MODBUSwww.mgeups.comT H E U N I N T E R R U P T I B

Page 30

Page 2 - 51029066FR/BB

Page 31

51029066FR/BB - Page 3IntroductionNous vous remercions d’avoir choisi les produits MGE UPS SYSTEMS pour la sécurité de vos équipements.La carte JBUS/

Page 32 - 4. Troubleshooting

Page 4 - 51029066FR/BBInformations et conseils.Signalisation visuelle.Action.Avant proposSuivre impérativement ces consignes.Conventions utilisées dan

Page 33 - 5. Index

51029066FR/BB - Page 5Sommaire1. Présentation1.1 Déballage et vérification du contenu ...

Page 34 - Page 34 - 51029066EN/BB

Page 4 - 51029066EN/BBInformation, advice, help.Visual indication.Action.ForewordImportant operations to be done.Pictograms used in this manualFederal

Page 35 - Carte de

Page 6 - 51029066FR/BB1. Présentation1.1 Déballage et vérification du contenuLe produit que vous venez d'acquérir secompose des éléments suivants

Page 36 - Page 2 - 51029066FR/BB

51029066FR/BB - Page 766061JBUS/MODBUS1.2 Vue d’ensembleBoîtier de paramétrage de la communicationJBUS/MODBUS (SA1).2413761. PrésentationPort de comm

Page 37

Page 8 - 51029066FR/BB1.3 Fonctions1. PrésentationLa carte de communication JBUS/MODBUS permet la transmission à un outil informatique d’un ensemble d

Page 38 - Avant propos

51029066FR/BB - Page 91. PrésentationProtocole JBUSLa description détaillée du protocole JBUS/MODBUS est disponible sur notre site www.mgeups.comLes

Page 39 - Sommaire

Page 10 - 51029066FR/BB2. Installation2.1 Configuration des paramètres de communication JBUS/MODBUSSi les valeurs par défaut (voir §1.4) des paramètre

Page 40 - 1. Présentation

51029066FR/BB - Page 112. Installation3 - Régler le terminal avec les paramètres de communication suivants : 9600 bauds, parité paire, 1 bit stop et

Page 41

Page 12 - 51029066FR/BB2. Installation2.2 Retour aux paramètres JBUS/MODBUS par défautPour revenir aux paramètres par défaut (voir §1.4) de communicat

Page 42

51029066FR/BB - Page 132.3 Configuration et raccordement de la liaison RS2322. InstallationConfiguration par défaut :Transmission des donnéesRéceptio

Page 43

Page 14 - 51029066FR/BB2. Installation2.4 Configuration et raccordement de la liaison RS485La liaison EIA RS485, en 2 fils ou en 4 fils, doit être pol

Page 44

51029066FR/BB - Page 152. InstallationLe boîtier SA2 est utilisé pour réaliser l'adaptation et la polarisation de la liaison RS485 :(tous sur OF

Page 45

51029066EN/BB - Page 5Contents1. Presentation1.1 Unpacking and checking contents ...

Page 46

Page 16 - 51029066FR/BB2. InstallationSchéma de principe d'une liaison inter-cellules en 2 fils5VRpRaRp0V5VRpRaRp0V5VRpRaRp0VL- L-L+ L+L- L-L+ L+

Page 47

51029066FR/BB - Page 172. InstallationConfiguration de la carte d'un équipement intermédiaire en 2 filsLiaison sans polarisation et sans adaptat

Page 48

Page 18 - 51029066FR/BB2. InstallationSchéma de principe d'une liaison inter-cellules en 4 fils5VRpRp0V5VRpRaRp0V5VRpRaRp0VT- R-T+ R+R- R-R+ R+23

Page 49

51029066FR/BB - Page 192. InstallationConfiguration de la carte d'un équipement intermédiaire en 4 filsLiaison sans polarisation et sans adaptat

Page 50

Page 20 - 51029066FR/BB2. Installation2.5 Mise en placeIl n’est pas nécessaire de mettre l’ASI ou leSTS hors-tension.1. Dévisser et ôter le plastron d

Page 51

51029066FR/BB - Page 213. UtilisationLa carte de communication JBUS/MODBUS peut être insérée dans tous les produits équipés de slots de communication

Page 52

Page 22 - 51029066FR/BB3. UtilisationTable des mesuresDescription de la grandeur physique Mot UnitéI réseau 1 100 AI utilisation 109 AU réseau 1 115 V

Page 53

51029066FR/BB - Page 233.2 Dans Galaxy 3000Table des états3. UtilisationDescription de l’état Etat à 0 Etat à 1 Mot BitCharge protégée non oui 40 0AS

Page 54

Page 24 - 51029066FR/BB3. UtilisationDescription de l’état Etat à 0 Etat à 1 Mot BitFréquence réseau 2 hors tolérance non oui 46 9Tension réseau 2 hor

Page 55 - 3. Utilisation

51029066FR/BB - Page 25Table des mesuresDescription de la grandeur physique Mot UnitéI1 (I phase 1) réseau 1 100 AI2 (I phase 2) réseau 1 101 AI3 (I

Page 56

Page 6 - 51029066EN/BB1. Presentation1.1 Unpacking and checking contentsThe product is made up of the followingelements:◗ JBUS/MODBUS communication ca

Page 57

Page 26 - 51029066FR/BB3. Utilisation3.3 Dans Galaxy PWTable des étatsDescription de l’état Etat à 0 Etat à 1 Mot BitCharge protégée non oui 40 0ASI c

Page 58

51029066FR/BB - Page 27Description de l’état Etat à 0 Etat à 1 Mot BitInterrupteur d’entrée réseau 1 (Q1) fermé ouvert 44 3Tension réseau 1 hors tolé

Page 59

Page 28 - 51029066FR/BB3. UtilisationTable des mesuresDescription de la grandeur physique Mot UnitéI1 (I phase 1) réseau 1 100 AI2 (I phase 2) réseau

Page 60

51029066FR/BB - Page 29Description de la grandeur physique Mot UnitéAutonomie nominale 148 mnAutonomie batterie 149 mnTempérature local batterie 14A

Page 61

Page 30 - 51029066FR/BB3. UtilisationDescription de l’état Etat à 0 Etat à 1 Mot BitSource 2 hors tolérance non oui 1002 ETransfert valide non oui 100

Page 62

51029066FR/BB - Page 313. UtilisationTable des mesuresDescription de la grandeur physique Mot UnitéU12 source 1 1100 VU23 source 1 1101 VU31 source 1

Page 63

Page 32 - 51029066FR/BB4. MaintenanceProblèmeLe voyant de diagnostic 6reste éteint en permanence.Le voyant de diagnostic 6reste allumé en permanen

Page 64

51029066FR/BB - Page 33AAdaptation de la ligne ... 14-19BBoîtier SA2 de configuration de la liaison RS485

Page 65

Page 34 - 51029066FR/BB

Page 66 - 4. Maintenance

51029066EN/BB - Page 766061JBUS/MODBUS1.2 OverviewSwitches for JBUS/MODBUS settings (SA1).2413761. PresentationRS232 communication port.Diagnostic LE

Page 67

Page 8 - 51029066EN/BB1.3 Functions1. PresentationThe JBUS/MODBUS communication card provides UPS (Uninterruptible Power Supply) and STS (Static Trans

Page 68 - Page 34 - 51029066FR/BB

51029066EN/BB - Page 91. PresentationJBUS ProtocolDetailed description of the JBUS/MODBUS protocol is available on our Web site www.mgeups.comThe sta