Instruction Booklet IB 70-8698
Instruction Manual for the Eaton RTC-100
Automatic Transfer Switch Controller
EATON CORPORATION www.eaton.com
Effective December 2009
4.1.3 Reset Pushbutton
If, during normal operation, a transfer (from utility to generator
or from generator to utility) does NOT occur when it should, the
“CONNECTED” LED’s (WHITE or YELLOW depending on which
source should be connected) will flash (see Figure 4). Once the root
cause of the failure to transfer has been corrected, the “RESET”
pushbutton (see Figure 4) needs to be momentarily depressed
(about 1 second) to reset the board.
Figure 4. Reset Pushbutton and Connected LEDs.
“Connected“ LED’s